FJ2M200
Circuit Breakers
CIRCUIT BREAKER
FJ2M200
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0
-
Trip Delay Time In Seconds Per Rated Continuous Current
110.000 minimum at 200 pct and 40.000 maximum at 300 pct all locations
-
Frequency In Hertz
60.0
-
Thread Series Designator
unc
-
Body Width
3.000 inches nominal
-
Mounting Facility Type And Quantity
2 threaded hole
-
Special Handling Feature
magnetic
-
Maximum Continuous Load Current Rating Per Pole
200.0 amperes ac and 200.0 amperes dc all locations
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac and 250.0 dc all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac and 10000.0 dc all locations
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Nominal Thread Size
0.164 inches
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Terminal Type And Quantity
4 compression
-
Body Style
20b multipole-single actuator type
-
Body Length
6.000 inches nominal
-
Body Height
3.594 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Width
1.500 inches nominal
-
Fragility Factor
moderately rugged
-
Boss Height
0.219 inches nominal
-
Pole Quantity
2
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Trip Release Method
thermal-magnetic all locations