AM3-B3-A3-A
Circuit Breakers
CIRCUIT BREAKER
AM3-B3-A3-A
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Manual Actuator Type And Quantity
3 toggle
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
1.25 amperes dc first location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Frequency In Hertz
60.0 third location
-
Arc Quenching Method
magnetic blowout
-
Main Contact Tripping Mechanism Type
trip free
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc first location
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Nominal Thread Size
0.138 inches
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac third location
-
Trip Delay Time In Seconds Per Rated Continuous Current
4.000 minimum at 200 pct third location and 10.000 maximum at 200 pct third location
-
Mounting Facility Type And Quantity
6 threaded hole
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Body Width
2.240 inches minimum and 2.260 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
4.0 amperes ac third location
-
Frequency In Hertz
60.0 second location
-
Body Style
multipole-multiple actuator type
-
Trip Release Method
magnetic-hydraulic all locations
-
Thread Quantity Per Inch
32
-
Internal Trip Release Configuration
series trip all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac second location
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Maximum Continuous Load Current Rating Per Pole
4.0 amperes ac second location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 dc first location
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Mounting Surface To Terminal End Distance
2.461 inches minimum and 2.481 inches maximum
-
Reset Method
manual
-
Actuator Position Designation
at each pole
-
Thread Series Designator
unc
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.150 minimum at 200 pct first location and 0.550 maximum at 200 pct first location
-
Fragility Factor
moderately rugged
-
Terminal Type And Quantity
6 threaded stud
-
Case Material
plastic
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac third location
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac second location
-
Trip Delay Time In Seconds Per Rated Continuous Current
4.000 minimum at 200 pct second location and 10.000 maximum at 200 pct second location
Related Parts by Category
Related Parts by Manufacturer


AS6081 Methods