5-644-004

Circuit Breakers

CIRCUIT BREAKER

5-644-004

5925-00-147-0749

5925 - Circuit Breakers

Spx Corporation

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Fragility Factor

    moderately rugged

  • Special Handling Feature

    magnetic

  • Circuit Protection Type

    overcurrent all locations

  • Center To Center Distance Between Terminals Parallel To Width

    0.735 inches minimum and 0.765 inches maximum

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    2000.0 dc all locations

  • Pole Quantity

    2

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.100 minimum at 200 pct all locations and 1.700 maximum at 200 pct all locations

  • Unpackaged Unit Weight

    7.400 ounces

  • Terminal Type And Quantity

    4 threaded stud

  • External Actuator Linkage Arrangement

    one and two linked

  • Case Material

    plastic

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Inclosure Protection Type For Which Designed

    shockproof and vibrationproof and moisture resistant and corrosion resistant and fungus resistant

  • Boss Height

    0.150 inches nominal

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Maximum Continuous Load Current Rating Per Pole

    100.0 milliamperes dc second location

  • Internal Trip Release Configuration

    series trip all locations

  • Center To Center Distance Between Terminals Parallel To Length

    1.940 inches nominal

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.050 inches minimum and 2.070 inches maximum

  • Thread Quantity Per Inch

    32

  • Switch Current Rating And Type In Amps

    10.0 ac and 10.0 dc

  • Trip Release Method

    magnetic all locations

  • Body Style

    multipole-multiple actuator type

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 65.0 dc

  • Maximum Continuous Load Current Rating Per Pole

    50.0 amperes dc first location

  • Nominal Thread Size

    0.138 inches

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.735 inches minimum and 0.765 inches maximum

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Operating Voltage Type And Rating Per Pole In Volts

    32.0 dc all locations

  • Switch Location And Position Designation

    internal at each pole

  • Manual Actuator Type And Quantity

    2 toggle

  • Body Width

    1.515 inches maximum

  • Switch Terminal Type

    pin

  • Thread Pitch Diameters

    +0.1177/+0.1214 inches

  • Body Length

    2.480 inches minimum and 2.500 inches maximum

  • Mounting Surface To Terminal End Distance

    2.625 inches maximum

  • Auxiliary Switch Function And Quantity

    1 alarm

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.