Technical Characteristics
- 
                                    Bushing Length0.250 inches nominal 
- 
                                    Thread Series Designatorunc 
- 
                                    Reset Methodmanual 
- 
                                    Test Data Document81349-mil-c-5809 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type 
- 
                                    Actuator Position Designationat pole one 
- 
                                    Actuator Functiontrip-reset 
- 
                                    Terminal Type And Quantity2 screw 
- 
                                    Inclosure Protection Type For Which Designedmoisture resistant and explosion resistant 
- 
                                    Mounting Facility Type And Quantity2 threaded hole 
- 
                                    Thread Quantity Per Inch32 
- 
                                    Mounting Surface To Terminal End Distance2.000 inches maximum 
- 
                                    Circuit Protection Typeovercurrent single location 
- 
                                    Center To Center Distance Between Terminals Parallel To Length1.188 inches nominal 
- 
                                    Trip Release Methodthermal single location 
- 
                                    Manual Actuator Type And Quantity1 push-pull 
- 
                                    Pole Quantity1 
- 
                                    Case Materialmetal 
- 
                                    Body Length2.189 inches maximum 
- 
                                    Internal Trip Release Configurationseries trip single location 
- 
                                    Nominal Thread Size0.138 inches 
- 
                                    Operating Voltage Type And Rating Per Pole In Volts115.0 ac single location and 28.0 dc single location 
- 
                                    Trip Release Characteristictime delay single location 
- 
                                    Trip Release Ambient Temp Rating25.0 deg celsius nominal single location 
- 
                                    Main Contact Tripping Mechanism Typetrip free 
- 
                                    Maximum Continuous Load Current Rating Per Pole15.0 amperes ac single location and 15.0 amperes dc single location 
- 
                                    Frequency In Hertz400.0 single location 
- 
                                    ~1data on certain environmental and performance 
- 
                                    Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps3500.0 ac single location and 6000.0 dc single location 
- 
                                    Body Stylesingle pole type 
- 
                                    Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent138.0 single location 
- 
                                    Distance Between Centerlines Of Mounting Facilities Parallel To Body Length2.189 inches maximum 
- 
                                    Body Width0.750 inches maximum 
- 
                                    Trip Delay Time In Seconds Per Rated Continuous Current2.000 minimum at 400 pct single location and 55.000 maximum at 200 pct single location and 15.000 minimum at 200 pct single location and 7.000 maximum at 400 pct single location 
Related Parts by Category
Related Parts by Manufacturer
 
     Certified to
        Certified toAS6081 Methods
 
     
     
    
    
    
     

 
    