Technical Characteristics
- 
                                    
Case Material
plastic
 - 
                                    
Center To Center Distance Between Terminals Parallel To Length
1.625 inches nominal
 - 
                                    
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.250 inches nominal
 - 
                                    
Boss Height
0.125 inches nominal
 - 
                                    
Mounting Surface To Terminal End Distance
2.100 inches nominal
 - 
                                    
Pole Quantity
3
 - 
                                    
Mounting Facility Type And Quantity
6 threaded hole
 - 
                                    
Thread Quantity Per Inch
32
 - 
                                    
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac all locations
 - 
                                    
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac all locations
 - 
                                    
Circuit Protection Type
overcurrent all locations
 - 
                                    
Trip Release Characteristic
time delay all locations
 - 
                                    
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
 - 
                                    
Main Contact Tripping Mechanism Type
trip free
 - 
                                    
Manual Actuator Type And Quantity
3 toggle
 - 
                                    
Frequency In Hertz
400.0
 - 
                                    
Body Style
8c multipole-multiple actuator type
 - 
                                    
Body Length
2.250 inches nominal
 - 
                                    
Body Width
2.250 inches nominal
 - 
                                    
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
 - 
                                    
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.810 inches nominal
 - 
                                    
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
 - 
                                    
Trip Release Method
magnetic all locations
 - 
                                    
Reset Method
manual
 - 
                                    
Actuator Function
trip-reset
 - 
                                    
Actuator Position Designation
at each pole
 - 
                                    
External Actuator Linkage Arrangement
one, two, and three linked
 - 
                                    
Internal Trip Release Configuration
series trip all locations
 - 
                                    
Nominal Thread Size
0.138 inches
 - 
                                    
Trip Delay Time In Seconds Per Rated Continuous Current
1.500 minimum at 150 pct and 6.000 maximum at 150 pct all locations
 - 
                                    
Thread Series Designator
unc
 - 
                                    
Terminal Type And Quantity
6 threaded stud
 
Related Parts by Category
Related Parts by Manufacturer
    
        Certified toAS6081 Methods
    
    
    
    
    
    

    