APL1-1R0-6-1-153
Circuit Breakers
CIRCUIT BREAKER
APL1-1R0-6-1-153
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
- 
                                    Specification/Standard Data81349-mil-c-55629/2 government specification 
- 
                                    Fragility Factormoderately rugged 
- 
                                    Body Width0.730 inches minimum and 0.780 inches maximum 
- 
                                    Trip Release Methodmagnetic single location 
- 
                                    Switch Terminal Typetab, solder lug 
- 
                                    Center To Center Distance Between Terminals Parallel To Length1.660 inches minimum and 1.960 inches maximum 
- 
                                    Special Handling Featuremagnetic 
- 
                                    Operating Voltage Type And Rating Per Pole In Volts240.0 ac single location 
- 
                                    Inclosure Protection Type For Which Designedshock resistant and vibration resistant 
- 
                                    Thread Series Designatorunc 
- 
                                    Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps1000.0 ac single location 
- 
                                    Reset Methodmanual 
- 
                                    Distance Between Centerlines Of Mounting Facilities Parallel To Body Length2.046 inches minimum and 2.078 inches maximum 
- 
                                    Trip Delay Time In Seconds Per Rated Continuous Current0.135 minimum at 200 pct single location and 1.800 maximum at 200 pct single location 
- 
                                    Actuator Position Designationat pole one 
- 
                                    Storage Typegeneral purpose warehouse 
- 
                                    Actuator Functiontrip-reset 
- 
                                    Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent125.0 single location 
- 
                                    Main Contact Tripping Mechanism Typetrip free 
- 
                                    Arc Quenching Methodmagnetic blowout 
- 
                                    Body Stylesingle pole type 
- 
                                    Frequency In Hertz60.0 single location 
- 
                                    Thread Pitch Diameters+0.1177/+0.1214 inches 
- 
                                    Auxiliary Switch Function And Quantity1 alarm 
- 
                                    Body Length2.510 inches maximum 
- 
                                    Boss Height0.109 inches minimum and 0.171 inches maximum 
- 
                                    Switch Location And Position Designationinternal at pole one 
- 
                                    Case Materialplastic 
- 
                                    Terminal Type And Quantity2 threaded stud 
- 
                                    ~1data on certain environmental and performanc 
- 
                                    Test Data Document81349-mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type 
- 
                                    Mounting Facility Type And Quantity2 threaded hole 
- 
                                    Thread Quantity Per Inch32 
- 
                                    Circuit Protection Typeovercurrent single location 
- 
                                    Switch Current Rating And Type In Amps10.0 ac and 2.0 dc 
- 
                                    Mounting Surface To Terminal End Distance2.800 inches maximum 
- 
                                    Switch Contact Arrangementsingle pole, double throw 
- 
                                    Maximum Continuous Load Current Rating Per Pole15.0 amperes ac single location 
- 
                                    Switch Voltage Rating And Type In Volts250.0 ac and 50.0 dc 
- 
                                    Pole Quantity1 
- 
                                    Manual Actuator Type And Quantity1 toggle 
- 
                                    Internal Trip Release Configurationseries trip single location 
- 
                                    Nominal Thread Size0.138 inches 
- 
                                    Trip Release Characteristictime delay single location 
Related Parts by Category
Related Parts by Manufacturer
 
     Certified to
        Certified toAS6081 Methods
 
     
     
    
    
    
     

 
    