2266892-7
Circuit Breakers
CIRCUIT BREAKER
2266892-7
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
- 
                                    Body Stylemultipole-single actuator type 
- 
                                    Body Width1.875 inches maximum 
- 
                                    Case Materialmetal 
- 
                                    Center To Center Distance Between Terminals Parallel To Width0.625 inches nominal 
- 
                                    Pole Quantity3 
- 
                                    Mounting Facility Type And Quantity1 threaded bushing 
- 
                                    Thread Quantity Per Inch32 
- 
                                    Maximum Continuous Load Current Rating Per Pole20.0 amperes ac 
- 
                                    Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps500.0 ac 
- 
                                    Circuit Protection Typeovercurrent 
- 
                                    Actuator Functiontrip-reset 
- 
                                    Actuator Position Designationat pole two 
- 
                                    Internal Trip Release Configurationseries trip 
- 
                                    Trip Delay Time In Seconds Per Rated Continuous Current2.500 minimum at 150 pct and 15.000 maximum at 150 pct and 0.850 minimum at 200 pct and 4.500 maximum at 200 pct and 0.400 minimum at 250 pct and 1.200 maximum at 250 pct and 0.200 minimum at 300 pct and 1.000 maximum at 300 pct 
- 
                                    Inclosure Protection Type For Which Designedhermetically sealed 
- 
                                    Frequency In Hertz60.0 
- 
                                    Bushing Length0.375 inches maximum 
- 
                                    Body Length1.500 inches maximum 
- 
                                    Center To Center Distance Between Terminals Parallel To Length0.875 inches nominal 
- 
                                    Mounting Surface To Terminal End Distance1.780 inches maximum 
- 
                                    Operating Voltage Type And Rating Per Pole In Volts120.0 ac 
- 
                                    Trip Release Methodmagnetic-hydraulic 
- 
                                    Trip Release Characteristictime delay 
- 
                                    Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent125.0 
- 
                                    Reset Methodmanual 
- 
                                    Main Contact Tripping Mechanism Typetrip free 
- 
                                    Manual Actuator Type And Quantity1 toggle 
- 
                                    Nominal Thread Size0.375 inches 
- 
                                    Thread Series Designatorunef 
- 
                                    Terminal Type And Quantity6 wire hook 
Related Parts by Category
Related Parts by Manufacturer
 
     Certified to
        Certified toAS6081 Methods
 
     
     
    
    
    
     

 
    