JA2-B3-A-10-2
Circuit Breakers
CIRCUIT BREAKER
JA2-B3-A-10-2
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
- 
                                    Distance Between Centerlines Of Mounting Facilities Parallel To Body Width0.745 inches minimum and 0.755 inches maximum 
- 
                                    Case Materialplastic 
- 
                                    Fragility Factormoderately rugged 
- 
                                    Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps1000.0 dc all locations 
- 
                                    Circuit Protection Typeovercurrent all locations 
- 
                                    Pole Quantity2 
- 
                                    Thread Series Designatorunc 
- 
                                    Actuator Position Designationat each pole 
- 
                                    Mounting Surface To Terminal End Distance1.835 inches minimum and 1.845 inches maximum 
- 
                                    Reset Methodmanual 
- 
                                    Center To Center Distance Between Terminals Parallel To Length1.555 inches minimum and 1.565 inches maximum 
- 
                                    Storage Typegeneral purpose warehouse 
- 
                                    Trip Release Characteristictime delay all locations 
- 
                                    Actuator Functiontrip-reset 
- 
                                    Internal Trip Release Configurationseries trip all locations 
- 
                                    Mounting Facility Type And Quantity4 threaded hole 
- 
                                    Thread Quantity Per Inch32 
- 
                                    Body Length1.985 inches minimum and 2.015 inches maximum 
- 
                                    Trip Release Methodmagnetic-hydraulic all locations 
- 
                                    Body Stylemultipole-multiple actuator type 
- 
                                    Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent125.0 all locations 
- 
                                    Boss Height0.125 inches minimum and 0.135 inches maximum 
- 
                                    Trip Delay Time In Seconds Per Rated Continuous Current1.000 minimum at 200 pct all locations and 12.000 maximum at 200 pct all locations 
- 
                                    Nominal Thread Size0.138 inches 
- 
                                    Main Contact Tripping Mechanism Typetrip free 
- 
                                    Arc Quenching Methodmagnetic blowout 
- 
                                    Body Width1.468 inches minimum and 1.532 inches maximum 
- 
                                    Center To Center Distance Between Terminals Parallel To Width0.745 inches minimum and 0.755 inches maximum 
- 
                                    Operating Voltage Type And Rating Per Pole In Volts32.0 dc all locations 
- 
                                    Terminal Type And Quantity4 tab, solder lug 
- 
                                    Distance Between Centerlines Of Mounting Facilities Parallel To Body Length1.655 inches minimum and 1.665 inches maximum 
- 
                                    Manual Actuator Type And Quantity2 toggle 
- 
                                    Inclosure Protection Type For Which Designeddustproof and fungus resistant 
- 
                                    External Actuator Linkage Arrangementone and two linked 
- 
                                    Maximum Continuous Load Current Rating Per Pole10.0 amperes dc all locations 
Related Parts by Category
Related Parts by Manufacturer
 
     Certified to
        Certified toAS6081 Methods
 
     
     
    
    
    
     

 
    


