2TC4-20
Circuit Breakers
CIRCUIT BREAKER
2TC4-20
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
- 
                                    Fragility Factormoderately rugged 
- 
                                    Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps2000.0 ac single location and 6000.0 dc single location 
- 
                                    Thread Series Designatorunc 
- 
                                    Reset Methodmanual 
- 
                                    Mounting Facility Type And Quantity1 threaded bushing w/panel seal 
- 
                                    Actuator Position Designationat pole one 
- 
                                    Body Width0.532 inches minimum and 0.592 inches maximum 
- 
                                    Trip Delay Time In Seconds Per Rated Continuous Current5.000 minimum at 200 pct single location and 15.000 maximum at 200 pct single location 
- 
                                    Storage Typegeneral purpose warehouse 
- 
                                    Actuator Functiontrip-reset 
- 
                                    Mounting Surface To Terminal End Distance1.282 inches minimum and 1.342 inches maximum 
- 
                                    Body Length0.720 inches minimum and 0.780 inches maximum 
- 
                                    Thread Quantity Per Inch32 
- 
                                    Circuit Protection Typeovercurrent single location 
- 
                                    Trip Release Methodthermal single location 
- 
                                    Manual Actuator Type And Quantity1 push-pull 
- 
                                    Pole Quantity1 
- 
                                    Inclosure Protection Type For Which Designedexplosion proof and fungus resistant 
- 
                                    Internal Trip Release Configurationseries trip single location 
- 
                                    Nominal Thread Size0.138 inches 
- 
                                    Operating Voltage Type And Rating Per Pole In Volts120.0 ac single location and 28.0 dc single location 
- 
                                    Trip Release Characteristictime delay single location 
- 
                                    Trip Release Ambient Temp Rating25.0 deg celsius nominal single location 
- 
                                    Main Contact Tripping Mechanism Typetrip free 
- 
                                    Frequency In Hertz400.0 single location 
- 
                                    Body Stylesingle pole type 
- 
                                    Unpackaged Unit Weight26.0 grams 
- 
                                    Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent138.0 single location 
- 
                                    Maximum Continuous Load Current Rating Per Pole20.0 amperes ac single location and 20.0 amperes dc single location 
- 
                                    Terminal Type And Quantity2 tab w/screw 
- 
                                    Center To Center Distance Between Terminals Parallel To Length0.674 inches minimum and 0.734 inches maximum 
- 
                                    Bushing Length0.220 inches minimum and 0.280 inches maximum 
- 
                                    Case Materialplastic 
Related Parts by Category
Related Parts by Manufacturer
 
     Certified to
        Certified toAS6081 Methods
 
     
     
    
    
    
     

 
    