Technical Characteristics
- 
                                    Frequency In Hertz60.0 
- 
                                    Trip Delay Time In Seconds Per Rated Continuous Current4.500 minimum at 150 pct and 55.000 maximum at 150 pct and 2.000 minimum at 200 pct and 20.000 maximum at 200 pct and 0.800 minimum at 300 pct and 6.000 maximum at 300 pct 
- 
                                    Nominal Thread Size0.138 inches 
- 
                                    Internal Trip Release Configurationseries trip 
- 
                                    External Actuator Linkage Arrangementone,two,and three linked 
- 
                                    Actuator Functiontrip-reset 
- 
                                    Manual Actuator Type And Quantity3 toggle 
- 
                                    Ultimate Trip Time Per Pole In Seconds3.000 minimum and 50.000 maximum 
- 
                                    Circuit Protection Typeovercurrent 
- 
                                    Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps1000.0 ac 
- 
                                    Mounting Facility Type And Quantity6 threaded hole 
- 
                                    Pole Quantity3 
- 
                                    Mounting Surface To Terminal End Distance1.880 inches nominal 
- 
                                    Boss Height0.130 inches nominal 
- 
                                    Distance Between Centerlines Of Mounting Facilities Parallel To Body Width0.750 inches nominal 
- 
                                    Center To Center Distance Between Terminals Parallel To Width0.750 inches nominal 
- 
                                    Center To Center Distance Between Terminals Parallel To Length1.560 inches nominal 
- 
                                    Case Materialplastic 
- 
                                    Body Width2.250 inches nominal 
- 
                                    Body Length2.000 inches nominal 
- 
                                    Terminal Type And Quantity6 tab,solder lug 
- 
                                    Thread Series Designatorunc 
- 
                                    Inclosure Protection Type For Which Designedfungus resistant and moisture resistant 
- 
                                    Actuator Position Designationat each pole 
- 
                                    Main Contact Tripping Mechanism Typetrip free 
- 
                                    Reset Methodmanual 
- 
                                    Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent125.0 
- 
                                    Trip Release Characteristictime delay 
- 
                                    Trip Release Methodmagnetic-hydraulic 
- 
                                    Operating Voltage Type And Rating Per Pole In Volts250.0 ac 
- 
                                    Maximum Continuous Load Current Rating Per Pole5.0 amperes ac 
- 
                                    Thread Quantity Per Inch32 
- 
                                    Distance Between Centerlines Of Mounting Facilities Parallel To Body Length1.660 inches nominal 
Related Parts by Category
Related Parts by Manufacturer
 
     Certified to
        Certified toAS6081 Methods
 
     
     
    
    
    
     

 
    