Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
3.625 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 ac all locations and 125.0 dc all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations and 5000.0 dc all locations
-
Boss Height
0.312 inches nominal
-
Nominal Thread Size
0.250 inches
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.500 inches nominal
-
Body Length
5.000 inches nominal
-
Case Material
plastic
-
Body Height
4.675 inches nominal
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Mounting Facility Type And Quantity
2 threaded hole
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Body Style
multipole-single actuator type
-
Maximum Continuous Load Current Rating Per Pole
35.0 amperes ac all locations and 35.0 amperes dc all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Terminal Type And Quantity
6 quick disconnect, female
-
Thread Quantity Per Inch
20
-
Frequency In Hertz
60.0 all locations
-
Body Width
5.000 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.250 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.688 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 200 pct all locations and 210.000 maximum at 200 pct all locations