58A80D62-1
Circuit Breakers
CIRCUIT BREAKER
58A80D62-1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
- 
                                    
Actuator Function
reset
 - 
                                    
Bushing Length
0.250 inches nominal
 - 
                                    
Pole Quantity
3
 - 
                                    
Circuit Protection Type
overcurrent all locations
 - 
                                    
Thread Series Designator
unc
 - 
                                    
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.812 inches nominal
 - 
                                    
Body Width
2.203 inches maximum
 - 
                                    
Reset Method
manual
 - 
                                    
Trip Release Characteristic
time delay all locations
 - 
                                    
Operating Voltage Type And Rating Per Pole In Volts
200.0 ac all locations and 30.0 dc all locations
 - 
                                    
Internal Trip Release Configuration
series trip all locations
 - 
                                    
Center To Center Distance Between Terminals Parallel To Length
1.486 inches nominal
 - 
                                    
Mounting Facility Type And Quantity
4 threaded hole
 - 
                                    
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 200 pct all locations and 70.000 maximum at 200 pct all locations
 - 
                                    
Thread Quantity Per Inch
32
 - 
                                    
Manual Actuator Type And Quantity
1 push-pull
 - 
                                    
Actuator Position Designation
at pole two
 - 
                                    
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.486 inches nominal
 - 
                                    
Body Style
multipole-single actuator type
 - 
                                    
Inclosure Protection Type For Which Designed
explosion proof and corrosion resistant and fungus resistant
 - 
                                    
Center To Center Distance Between Terminals Parallel To Width
1.188 inches nominal
 - 
                                    
Frequency In Hertz
400.0 all locations
 - 
                                    
Body Length
2.250 inches maximum
 - 
                                    
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac all locations and 1500.0 dc all locations
 - 
                                    
Case Material
plastic
 - 
                                    
Trip Release Method
thermal all locations
 - 
                                    
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac all locations and 5.0 amperes dc all locations
 - 
                                    
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
 - 
                                    
Nominal Thread Size
0.138 inches
 - 
                                    
Main Contact Tripping Mechanism Type
trip free
 - 
                                    
Terminal Type And Quantity
6 screw
 - 
                                    
Body Height
2.125 inches maximum
 - 
                                    
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 all locations
 
Related Parts by Category
Related Parts by Manufacturer
    
        Certified toAS6081 Methods
    
    
    
    
    
    

    