3XAM17-15-208AC400-55
Circuit Breakers
CIRCUIT BREAKER
3XAM17-15-208AC400-55
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
1.180 inches minimum and 1.200 inches maximum
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Terminal Type And Quantity
6 tab w/screw
-
Manual Actuator Type And Quantity
3 toggle
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac all locations
-
Case Material
plastic
-
Inclosure Protection Type For Which Designed
dustproof and fungus proof
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Nominal Thread Size
0.138 inches
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Mounting Facility Type And Quantity
6 threaded hole
-
Mounting Surface To Terminal End Distance
1.990 inches minimum and 2.010 inches maximum
-
Body Width
2.263 inches minimum and 2.283 inches maximum
-
Bushing Length
0.120 inches minimum and 0.130 inches maximum
-
Body Style
multipole-multiple actuator type
-
Trip Release Method
magnetic-hydraulic all locations
-
Thread Quantity Per Inch
32
-
Internal Trip Release Configuration
series trip all locations
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Reset Method
manual
-
Actuator Position Designation
at each pole
-
Thread Series Designator
unc
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac all locations
-
Fragility Factor
moderately rugged
-
Frequency In Hertz
400.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.802 inches minimum and 1.822 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
3.000 minimum at 200 pct all locations and 8.500 maximum at 200 pct all locations
Related Parts by Category
Related Parts by Manufacturer


AS6081 Methods