AM4-C3C3A3A3-15-15-10-10-P

Circuit Breakers

CIRCUIT BREAKER

AM4-C3C3A3A3-15-15-10-10-P

5925-01-078-6448

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac first location

  • Fragility Factor

    moderately rugged

  • Unpackaged Unit Weight

    1.200 pounds

  • Trip Release Characteristic

    instantaneous all locations

  • Circuit Protection Type

    overcurrent all locations

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Frequency In Hertz

    400.0 first location

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Frequency In Hertz

    50.0 third location or 60.0 third location

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Mounting Surface To Terminal End Distance

    2.331 inches minimum and 2.492 inches maximum

  • Thread Quantity Per Inch

    32

  • Mounting Facility Type And Quantity

    8 threaded hole

  • Trip Release Method

    magnetic-hydraulic all locations

  • Body Style

    multipole-multiple actuator type

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac second location

  • External Actuator Linkage Arrangement

    one, two, three, and four linked

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 fourth location

  • Terminal Type And Quantity

    8 threaded stud

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac fourth location

  • Nominal Thread Size

    0.138 inches

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Frequency In Hertz

    400.0 second location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 first location

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 third location

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 second location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Body Width

    2.990 inches minimum and 3.010 inches maximum

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac third location

  • Manual Actuator Type And Quantity

    4 toggle

  • Frequency In Hertz

    50.0 fourth location or 60.0 fourth location

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Case Material

    plastic

  • Pole Quantity

    4

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.