UPGH-14-725-2
Circuit Breakers
CIRCUIT BREAKER
UPGH-14-725-2
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Unpackaged Unit Weight
0.312 pounds
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Terminal Type And Quantity
6 quick disconnect, male
-
Manual Actuator Type And Quantity
2 toggle
-
Body Width
1.500 inches nominal
-
External Actuator Linkage Arrangement
one and two linked
-
Internal Trip Release Configuration
relay trip first location
-
Case Material
plastic
-
Boss Height
0.130 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Inclosure Protection Type For Which Designed
moisture resistant
-
Circuit Protection Type
overcurrent all locations
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes ac second location
-
Pole Quantity
2
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.660 inches nominal
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Center To Center Distance Between Terminals Parallel To Length
1.660 inches nominal
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Body Length
2.000 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Mounting Surface To Terminal End Distance
1.845 inches nominal
-
Mounting Facility Type And Quantity
4 threaded hole
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
1.0 amperes ac first location
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Internal Trip Release Configuration
series trip second location
-
Nominal Thread Size
0.138 inches
-
Frequency In Hertz
60.0 all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.150 minimum at 200 pct all locations and 1.500 maximum at 200 pct all locations
Related Parts by Category
Related Parts by Manufacturer


AS6081 Methods