CIRCUIT BREAKER
TED134080
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
4.880 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Terminal Type And Quantity
6 compression
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac all locations
-
Inclosure Protection Type For Which Designed
general purpose
-
Unthreaded Mounting Hole Diameter
0.188 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
480.0 ac all locations
-
Center To Center Distance Between Terminals Parallel To Length
5.250 inches nominal
-
Case Material
plastic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Body Width
4.125 inches nominal
-
Reset Method
manual
-
Body Length
6.310 inches nominal
-
Storage Type
general purpose warehouse
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Actuator Function
trip-reset
-
Body Height
3.380 inches nominal
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Boss Height
0.240 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
80.0 amperes ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.380 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.380 inches nominal
-
Trip Release Method
thermal-magnetic all locations
-
Actuator Position Designation
at pole two
-
Body Style
multipole-single actuator type
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.025 minimum at 100 pct all locations and 11.000 maximum at 100 pct all locations