MIL-C-17361
Circuit Breakers
CIRCUIT BREAKER
MIL-C-17361
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
- 
                                    
Frequency In Hertz
60.0
 - 
                                    
Body Style
17b multipole-single actuator type
 - 
                                    
Body Width
9.000 inches maximum
 - 
                                    
Case Material
plastic
 - 
                                    
Unthreaded Mounting Hole Diameter
0.250 inches nominal
 - 
                                    
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
17.000 inches nominal
 - 
                                    
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
5.000 inches nominal
 - 
                                    
Boss Height
0.250 inches nominal
 - 
                                    
Pole Quantity
3
 - 
                                    
Special Handling Feature
magnetic
 - 
                                    
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations
 - 
                                    
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
100000.0 ac all locations
 - 
                                    
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
130.0
 - 
                                    
Actuator Function
trip-reset
 - 
                                    
Actuator Position Designation
at pole two
 - 
                                    
Body Length
17.937 inches nominal
 - 
                                    
Center To Center Distance Between Terminals Parallel To Length
15.125 inches nominal
 - 
                                    
Center To Center Distance Between Terminals Parallel To Width
3.000 inches nominal
 - 
                                    
Fragility Factor
moderately rugged
 - 
                                    
Mounting Surface To Terminal End Distance
9.687 inches maximum
 - 
                                    
Arc Quenching Method
air
 - 
                                    
Mounting Facility Type And Quantity
6 unthreaded hole
 - 
                                    
Storage Type
general purpose warehouse
 - 
                                    
Maximum Continuous Load Current Rating Per Pole
400.0 amperes ac all locations
 - 
                                    
Circuit Protection Type
overcurrent all locations
 - 
                                    
Trip Release Method
thermal-magnetic all locations
 - 
                                    
Trip Release Characteristic
instantaneous and time delay all locations
 - 
                                    
Reset Method
manual
 - 
                                    
Main Contact Tripping Mechanism Type
trip free
 - 
                                    
Manual Actuator Type And Quantity
1 toggle
 - 
                                    
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
 - 
                                    
Trip Delay Time In Seconds Per Rated Continuous Current
20.000 minimum at 600 pct and 32.000 maximum at 600 pct all locations
 - 
                                    
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant
 - 
                                    
Terminal Type And Quantity
6 threaded stud
 - 
                                    
Nondefinitive Spec/Std Data
aqb-lf400 type
 
Related Parts by Category
Related Parts by Manufacturer
    
        Certified toAS6081 Methods
    
    
    
    
    
    

    