AP12-1R-9065-1
Circuit Breakers
CIRCUIT BREAKER
AP12-1R-9065-1
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Position Designation
between pole one and two
-
Body Length
1.500 inches maximum
-
Manual Actuator Type And Quantity
1 toggle
-
Case Material
metal
-
Body Style
multipole-single actuator type
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Switch Contact Arrangement
single pole, double throw
-
Terminal Type And Quantity
4 wire hook
-
Mounting Surface To Terminal End Distance
1.780 inches maximum
-
Trip Release Method
magnetic all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Thread Quantity Per Inch
32
-
Nominal Thread Size
0.375 inches
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Internal Trip Release Configuration
series trip all locations
-
Actuator Function
trip-reset
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Trip Release Characteristic
time delay all locations
-
Switch Location And Position Designation
internal at pole two
-
Storage Type
general purpose warehouse
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Reset Method
manual
-
Pole Quantity
2
-
Circuit Protection Type
overcurrent all locations
-
Special Handling Feature
magnetic
-
Bushing Length
0.380 inches maximum
-
Features Provided
high inrush protection
-
Inclosure Protection Type For Which Designed
hermetically sealed and shock resistant and vibration resistant
-
Auxiliary Switch Function And Quantity
1 alarm
-
Switch Voltage Rating And Type In Volts
120.0 ac and 50.0 dc
-
Thread Series Designator
unef
-
Switch Terminal Type
pin
-
Body Width
1.250 inches maximum
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Switch Current Rating And Type In Amps
0.5 ac and 0.5 dc
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.900 minimum at 200 pct all locations and 4.500 maximum at 200 pct all locations
Related Parts by Category
Related Parts by Manufacturer


AS6081 Methods