AM2-A7-A-4A/8A-115/2

Circuit Breakers

CIRCUIT BREAKER

AM2-A7-A-4A/8A-115/2

5925-01-175-8205

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Boss Height

    0.140 inches nominal

  • Pole Quantity

    2

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Iii Storage Type

    general purpose warehouse

  • Iii Special Handling Feature

    magnetic

  • Thread Quantity Per Inch

    32

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Nominal Thread Size

    0.138 inches

  • Frequency In Hertz

    60.0 all locations

  • Thread Series Designator

    unc

  • Terminal Type And Quantity

    6 threaded stud

  • Mounting Surface To Terminal End Distance

    2.471 inches nominal

  • Body Style

    8c multipole-multiple actuator type

  • Body Length

    2.500 inches nominal

  • Body Width

    1.500 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    1.938 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.062 inches nominal

  • Iii Fragility Factor

    moderately rugged

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.150 minimum at 200 pct and 1.500 maximum at 200 pct all locations

  • Internal Trip Release Configuration

    series trip w/dual rating all locations

  • External Actuator Linkage Arrangement

    one and two linked

  • Actuator Position Designation

    at each pole

  • Actuator Function

    trip-reset

  • Manual Actuator Type And Quantity

    2 toggle

  • Main Contact Tripping Mechanism Type

    trip free

  • Reset Method

    manual

  • Trip Release Method

    magnetic-hydraulic all locations

  • Circuit Protection Type

    overcurrent all locations

  • Maximum Continuous Load Current Rating Per Pole

    1.5 amperes ac and 3.0 amperes ac all locations

  • Iii Arc Quenching Method

    magnetic blowout

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.