205-111-1REC2-62F-3-751-AMO
Circuit Breakers
CIRCUIT BREAKER
205-111-1REC2-62F-3-751-AMO
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Terminal Type And Quantity
6 threaded stud
-
Fragility Factor
moderately rugged
-
Switch Terminal Type
tab, solder lug
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Switch Location And Position Designation
internal at pole three
-
Boss Height
0.150 inches nominal
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Center To Center Distance Between Terminals Parallel To Length
1.940 inches nominal
-
Body Length
2.490 inches nominal
-
Case Material
plastic
-
Features Provided
high inrush protection
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.060 inches nominal
-
Manual Actuator Type And Quantity
3 toggle
-
Auxiliary Switch Function And Quantity
1 alarm
-
Inclosure Protection Type For Which Designed
moisture resistant and fungus proof and salt water resistant
-
Thread Series Designator
iso m
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac all locations
-
Mounting Surface To Terminal End Distance
2.475 inches nominal
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Thread Pitch In Millimeters
0.50
-
Arc Quenching Method
magnetic blowout
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
1000.0 all locations
-
Nominal Thread Size
3.0 millimeters
-
Body Width
2.265 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2100.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
0.75 amperes ac all locations
-
Mounting Facility Type And Quantity
6 threaded hole
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Switch Current Rating And Type In Amps
10.0 ac and 3.0 dc
-
Ultimate Trip Time Per Pole In Seconds
0.040 maximum all locations
-
Switch Contact Arrangement
single pole, double throw
-
Body Style
multipole-multiple actuator type
-
Trip Release Method
magnetic all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct all locations and 22.000 maximum at 200 pct all locations
Related Parts by Category
Related Parts by Manufacturer


AS6081 Methods