4310-050-15
Circuit Breakers
CIRCUIT BREAKER
4310-050-15
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Operating Voltage Type And Rating Per Pole In Volts
200.0 ac single location
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location
-
Pole Quantity
1
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Main Contact Tripping Mechanism Type
trip free
-
Center To Center Distance Between Terminals Parallel To Length
0.490 inches minimum and 0.510 inches maximum
-
Frequency In Hertz
400.0 single location
-
Manual Actuator Type And Quantity
1 push-pull
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.500 minimum at 200 pct single location and 40.000 maximum at 200 pct single location
-
Nominal Thread Size
0.438 inches
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Body Style
single pole type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 single location
-
Terminal Type And Quantity
2 tab w/screw
-
Body Width
0.593 inches maximum
-
Thread Series Designator
uns
-
Case Material
plastic
-
Inclosure Protection Type For Which Designed
corrosion resistant and moisture resistant
-
Fragility Factor
moderately rugged
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Reset Method
manual
-
End Item Identification
aircraft,eagle f-15
-
Actuator Position Designation
at pole one
-
Body Length
0.781 inches maximum
-
Storage Type
general purpose warehouse
-
Criticality Code Justification
feat
-
Actuator Function
trip-reset
-
Special Features
weapon system essential
-
Mounting Surface To Terminal End Distance
1.343 inches maximum
-
Bushing Length
0.240 inches minimum and 0.260 inches maximum
-
Thread Quantity Per Inch
32