MIL-C-55629/20
Circuit Breakers
CIRCUIT BREAKER
MIL-C-55629/20
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Width
0.735 inches minimum and 0.765 inches maximum
-
Mounting Surface To Terminal End Distance
2.232 inches nominal
-
Body Length
1.969 inches minimum and 2.031 inches maximum
-
Terminal Type And Quantity
2 tab w/screw
-
Thread Series Designator
un
-
Nonturn Device Length
0.115 inches minimum and 0.145 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes dc single location
-
Bushing Length
0.464 inches minimum and 0.526 inches maximum
-
Switch Location And Position Designation
internal at pole one
-
Case Material
plastic
-
Fragility Factor
moderately rugged
-
Trip Release Method
magnetic single location
-
Switch Terminal Type
tab, solder lug
-
Reset Method
manual
-
Nominal Thread Size
0.500 inches
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Nonturn Device Diameter
0.138 inches nominal
-
Nonturn Device Radius
0.641 inches minimum and 0.671 inches maximum
-
Body Style
single pole type
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc single location
-
Arc Quenching Method
magnetic blowout
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Trip Release Characteristic
time delay single location
-
Internal Trip Release Configuration
series trip single location
-
Manual Actuator Type And Quantity
1 toggle
-
Center To Center Distance Between Terminals Parallel To Length
1.499 inches minimum and 1.561 inches maximum
-
Pole Quantity
1
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Switch Contact Arrangement
single pole, double throw
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Switch Current Rating And Type In Amps
10.0 ac and 2.0 dc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 dc single location
-
Circuit Protection Type
overcurrent single location
-
Thread Quantity Per Inch
32
-
Nonturn Device Location
at 12 oclock
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.130 minimum at 200 pct single location and 1.500 maximum at 200 pct single location
Related Parts by Category
Related Parts by Manufacturer


AS6081 Methods