APG66-1-61-403-91
Circuit Breakers
CIRCUIT BREAKER
APG66-1-61-403-91
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Internal Trip Release Configuration
series trip all locations
-
Terminal Type And Quantity
4 screw
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Mounting Surface To Terminal End Distance
2.032 inches nominal
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.700 minimum at 125 pct all locations and 0.008 minimum at 1000 pct all locations and 12.000 maximum at 125 pct all locations and 0.100 maximum at 1000 pct all locations
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Nominal Thread Size
0.138 inches
-
Maximum Continuous Load Current Rating Per Pole
40.0 amperes ac all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Center To Center Distance Between Terminals Parallel To Length
1.530 inches nominal
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Body Width
1.515 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 ac all locations
-
Bushing Length
0.130 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.660 inches nominal
-
Thread Series Designator
unc
-
Reset Method
manual
-
Trip Release Characteristic
time delay all locations
-
Body Length
2.000 inches nominal
Related Parts by Category
Related Parts by Manufacturer


AS6081 Methods