219-2-1-62F-8-4-20-H
Circuit Breakers
CIRCUIT BREAKER
219-2-1-62F-8-4-20-H
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
External Actuator Linkage Arrangement
one and two linked
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.011 inches minimum and 1.041 inches maximum
-
Terminal Type And Quantity
4 threaded stud
-
Operating Voltage Type And Rating Per Pole In Volts
480.0 ac all locations
-
Manual Actuator Type And Quantity
2 toggle
-
Frequency In Hertz
50.0 all locations or 60.0 all locations
-
Arc Quenching Method
magnetic blowout
-
Main Contact Tripping Mechanism Type
trip free
-
Nominal Thread Size
0.138 inches
-
Center To Center Distance Between Terminals Parallel To Width
1.011 inches minimum and 1.041 inches maximum
-
Body Width
2.072 inches maximum
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Body Style
multipole-multiple actuator type
-
Trip Release Method
magnetic all locations
-
Center To Center Distance Between Terminals Parallel To Length
3.535 inches minimum and 3.565 inches maximum
-
Thread Quantity Per Inch
32
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.735 inches minimum and 2.765 inches maximum
-
Mounting Facility Type And Quantity
4 threaded hole
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Internal Trip Release Configuration
series trip all locations
-
Mounting Surface To Terminal End Distance
3.535 inches minimum and 3.565 inches maximum
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Case Material
plastic
-
Boss Height
0.205 inches minimum and 0.235 inches maximum
-
Body Length
5.785 inches minimum and 5.815 inches maximum
-
Reset Method
manual
-
Actuator Position Designation
at each pole
-
Thread Series Designator
unc
-
Pole Quantity
2
-
Inclosure Protection Type For Which Designed
dustproof
-
Circuit Protection Type
overcurrent all locations
-
Fragility Factor
moderately rugged
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct all locations and 18.000 maximum at 200 pct all locations
Related Parts by Category
Related Parts by Manufacturer