M55629/6-397

Circuit Breakers

CIRCUIT BREAKER

M55629/6-397

5925-01-303-4070

5925 - Circuit Breakers

Military Specifications

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Switch Terminal Type

    tab, solder lug

  • Center To Center Distance Between Terminals Parallel To Length

    1.660 inches minimum and 1.960 inches maximum

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Manual Actuator Type And Quantity

    3 toggle

  • Boss Height

    0.109 inches minimum and 0.171 inches maximum

  • End Item Identification

    an/sqq-89(v) unit 106

  • Case Material

    plastic

  • Terminal Type And Quantity

    6 threaded stud

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 50.0 dc

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Body Length

    2.479 inches minimum and 2.510 inches maximum

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Nominal Thread Size

    0.138 inches

  • Main Contact Tripping Mechanism Type

    trip free

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.719 inches minimum and 0.781 inches maximum

  • Maximum Continuous Load Current Rating Per Pole

    25.0 amperes ac all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    20.000 minimum at 200 pct all locations and 160.000 maximum at 200 pct all locations

  • Frequency In Hertz

    400.0 all locations

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Reset Method

    manual

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.046 inches minimum and 2.078 inches maximum

  • Switch Location And Position Designation

    internal at pole three

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Mounting Surface To Terminal End Distance

    2.522 inches minimum and 2.553 inches maximum

  • Thread Quantity Per Inch

    32

  • Center To Center Distance Between Terminals Parallel To Width

    0.719 inches minimum and 0.781 inches maximum

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Body Width

    2.205 inches minimum and 2.285 inches maximum

  • Trip Release Method

    magnetic all locations

  • Switch Current Rating And Type In Amps

    10.0 ac and 2.0 dc

  • Body Style

    multipole-multiple actuator type

  • Inclosure Protection Type For Which Designed

    fungus resistant

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...