MIL-C-55629/1
Circuit Breakers
CIRCUIT BREAKER
MIL-C-55629/1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Boss Height
0.140 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc single location
-
Specification/Standard Data
81349-mil-c-55629/1 government specification
-
Body Style
single pole type
-
Thread Pitch Diameters
+0.1177/+0.1214 inches
-
Body Length
2.510 inches maximum
-
Inclosure Protection Type For Which Designed
hermetically sealed and shock resistant and vibration resistant
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 dc single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0 single location
-
Pole Quantity
1
-
Mounting Surface To Terminal End Distance
2.553 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Trip Release Characteristic
time delay single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Case Material
plastic
-
Terminal Type And Quantity
2 threaded stud
-
Test Data Document
81349-mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
~1
data on certain environmental and performanc
-
Fragility Factor
moderately rugged
-
Body Width
0.730 inches minimum and 0.780 inches maximum
-
Trip Release Method
magnetic single location
-
Center To Center Distance Between Terminals Parallel To Length
1.660 inches minimum and 1.960 inches maximum
-
Special Handling Feature
magnetic
-
Thread Series Designator
unc
-
Maximum Continuous Load Current Rating Per Pole
6.0 amperes dc single location
-
Reset Method
manual
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.046 inches minimum and 2.078 inches maximum
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Mounting Facility Type And Quantity
2 threaded hole
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.500 minimum at 200 pct single location and 20.000 maximum at 200 pct single location
Related Parts by Category
Related Parts by Manufacturer


AS6081 Methods