MIL-C-39019C
Circuit Breakers
CIRCUIT BREAKER
MIL-C-39019C
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
~1
type data on certain environmental and performan
-
Test Data Document
81349-mil-c-39019c specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general
-
Trip Release Method
magnetic single location
-
Reset Method
manual
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
200.0 single location
-
Circuit Protection Type
overcurrent single location
-
Body Length
1.700 inches maximum
-
Pole Quantity
1
-
Maximum Continuous Load Current Rating Per Pole
12.5 amperes ac single location
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
Main Contact Tripping Mechanism Type
trip free
-
Frequency In Hertz
400.0 single location
-
Special Test Features
81349-m39019/01-252s
-
Body Style
single pole type
-
Center To Center Distance Between Terminals Parallel To Length
0.906 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 minimum at 200 pct single location and 9.000 maximum at 200 pct single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac single location and 500.0 dc single location
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac single location and 50.0 dc single location
-
Body Width
1.562 inches nominal
-
Specification/Standard Data
81349-mil-c-39019c government specification
-
Bushing Length
0.380 inches maximum
Related Parts by Category
Related Parts by Manufacturer


AS6081 Methods