MIL-C-55629/6
Circuit Breakers
CIRCUIT BREAKER
MIL-C-55629/6
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Test Data Document
81349-mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Frequency In Hertz
400.0 all locations
-
Auxiliary Switch Function And Quantity
1 alarm
-
Body Length
2.510 inches maximum
-
Manual Actuator Type And Quantity
3 toggle
-
Specification/Standard Data
81349-mil-c-55629/6 government specification
-
Switch Location And Position Designation
internal at pole one
-
Terminal Type And Quantity
6 threaded stud
-
~1
data on certain environmental and performanc
-
Switch Terminal Type
tab, solder lug
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
1.660 inches minimum and 1.960 inches maximum
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.046 inches minimum and 2.078 inches maximum
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac all locations
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Body Width
2.205 inches minimum and 2.285 inches maximum
-
Trip Release Method
magnetic all locations
-
Switch Current Rating And Type In Amps
10.0 ac and 2.0 dc
-
Body Style
multipole-multiple actuator type
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Switch Contact Arrangement
single pole, double throw
-
Mounting Surface To Terminal End Distance
2.553 inches maximum
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Mounting Facility Type And Quantity
6 threaded hole
-
Case Material
metal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Nominal Thread Size
0.138 inches
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Boss Height
0.140 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
20.000 minimum at 200 pct all locations and 160.000 maximum at 200 pct all locations
Related Parts by Category
Related Parts by Manufacturer


AS6081 Methods