NSN: 5925-00-175-2580
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Trip Release Method
magnetic single location
-
Center To Center Distance Between Terminals Parallel To Length
0.750 inches nominal
-
Inclosure Protection Type For Which Designed
dustproof
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
100.0 dc single location
-
Body Width
0.766 inches nominal
-
Thread Series Designator
unc
-
Body Length
2.203 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Nominal Thread Size
0.164 inches
-
Mounting Surface To Terminal End Distance
1.438 inches nominal
-
Body Style
single pole type
-
Trip Delay Time In Seconds Per Rated Continuous Current
80.000 nominal at 200 pct single location
-
Special Features
115 w ac application possible where very high rupture capacity is not a critical consideration
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes dc single location
-
Operating Voltage Type And Rating Per Pole In Volts
30.0 dc single location
-
Case Material
plastic
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.813 inches nominal
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Terminal Type And Quantity
2 screw
-
Mounting Facility Type And Quantity
2 threaded hole
-
Circuit Protection Type
overcurrent single location
-
Arc Quenching Method
air
-
Unpackaged Unit Weight
1.850 ounces
-
Pole Quantity
1
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location