Technical Characteristics
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 ac single location
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location
-
Thread Series Designator
unef
-
Mounting Surface To Terminal End Distance
1.605 inches maximum
-
Circuit Protection Type
overcurrent single location
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac single location
-
Body Width
0.625 inches maximum
-
Body Style
single pole type
-
Frequency In Hertz
400.0 single location
-
Arc Quenching Method
magnetic blowout
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Trip Release Characteristic
time delay single location
-
Body Length
1.500 inches maximum
-
Internal Trip Release Configuration
series trip single location
-
Manual Actuator Type And Quantity
1 toggle
-
Case Material
metal
-
Pole Quantity
1
-
Bushing Length
0.375 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Inclosure Protection Type For Which Designed
hermetically sealed
-
Nominal Thread Size
0.375 inches
-
Actuator Function
trip-reset
-
Storage Type
general purpose warehouse
-
Unpackaged Unit Weight
2.100 ounces
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Reset Method
manual
-
Special Handling Feature
magnetic
-
Terminal Type And Quantity
2 wire hook
-
Trip Release Method
magnetic single location
-
Fragility Factor
moderately rugged
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.750 minimum at 125 pct single location and 3.000 maximum at 125 pct single location
Related Parts by Category
Related Manufacturers


AS6081 Methods