NSN: 5925-01-107-0844
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
9.531 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
2.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
2.750 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
400.0 amperes ac all locations and 400.0 amperes dc all locations
-
Center To Center Distance Between Terminals Parallel To Length
9.531 inches nominal
-
Body Length
10.750 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
25000.0 ac all locations and 10000.0 dc all locations
-
Case Material
plastic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Body Height
4.062 inches nominal
-
Actuator Position Designation
at pole two
-
Body Style
multipole-single actuator type
-
Boss Height
0.250 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Terminal Type And Quantity
6 compression
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Actuator Function
trip-reset
-
Unthreaded Mounting Hole Diameter
0.312 inches nominal
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Body Width
8.250 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations and 250.0 dc all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
90.000 minimum at 200 pct all locations and 450.000 maximum at 200 pct all locations
Related Parts by Category
Related Manufacturers


AS6081 Methods