NSN: 5925-01-155-2507
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
1
-
Boss Height
0.250 inches nominal
-
~1
data on certain environmental and performance
-
Test Data Document
81349-mil-c-5809 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Fragility Factor
moderately rugged
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant
-
Maximum Continuous Load Current Rating Per Pole
7.5 amperes ac single location and 7.5 amperes dc single location
-
Thread Series Designator
unc
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.812 inches nominal
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Mounting Surface To Terminal End Distance
1.343 inches maximum
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Operating Voltage Type And Rating Per Pole In Volts
200.0 ac single location and 28.0 dc single location
-
Trip Release Characteristic
time delay single location
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Main Contact Tripping Mechanism Type
trip free
-
Unpackaged Unit Weight
0.087 pounds
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac single location and 3500.0 dc single location
-
Frequency In Hertz
400.0 single location
-
Body Style
single pole type
-
Body Length
2.187 inches maximum
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 single location
-
Center To Center Distance Between Terminals Parallel To Length
0.906 inches nominal
-
Terminal Type And Quantity
2 tab w/screw
-
Body Width
0.750 inches maximum
-
Specification/Standard Data
96906-ms24509 government standard
-
End Item Identification
2350-01-091-5405
-
Case Material
plastic
-
Trip Delay Time In Seconds Per Rated Continuous Current
20.000 minimum at 200 pct single location and 70.000 maximum at 200 pct single location
Related Parts by Category
Related Manufacturers


AS6081 Methods