NSN: 5925-01-189-1873
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
- 
                                    
Body Style
12a single pole type
 - 
                                    
Center To Center Distance Between Terminals Parallel To Length
6.125 inches nominal
 - 
                                    
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
5.125 inches nominal
 - 
                                    
Boss Height
0.125 inches nominal
 - 
                                    
Mounting Surface To Terminal End Distance
3.000 inches nominal
 - 
                                    
Pole Quantity
1
 - 
                                    
Mounting Facility Type And Quantity
2 unthreaded hole
 - 
                                    
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac single location
 - 
                                    
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
 - 
                                    
Reset Method
manual
 - 
                                    
Manual Actuator Type And Quantity
1 toggle
 - 
                                    
Actuator Function
trip-reset
 - 
                                    
Actuator Position Designation
at pole one
 - 
                                    
Inclosure Protection Type For Which Designed
general purpose
 - 
                                    
Criticality Code Justification
feat
 - 
                                    
Main Contact Tripping Mechanism Type
trip free
 - 
                                    
Trip Delay Time In Seconds Per Rated Continuous Current
40.000 minimum at 200 pct single location and 125.000 maximum at 200 pct
 - 
                                    
Trip Release Ambient Temp Rating
40.0 deg celsius nominal single location
 - 
                                    
Special Features
rear terminal connection
 - 
                                    
Frequency In Hertz
60.0 single location
 - 
                                    
Terminal Type And Quantity
1 compression and 1 quick disconnect, male
 - 
                                    
Trip Release Characteristic
instantaneous single location and time delay
 - 
                                    
Trip Release Method
thermal-magnetic single location
 - 
                                    
Circuit Protection Type
overcurrent single location
 - 
                                    
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac single location
 - 
                                    
Operating Voltage Type And Rating Per Pole In Volts
480.0 ac single location
 - 
                                    
Storage Type
general purpose warehouse
 - 
                                    
Unthreaded Mounting Hole Diameter
0.190 inches nominal
 - 
                                    
Case Material
plastic
 - 
                                    
Body Width
4.469 inches nominal
 - 
                                    
Body Length
7.000 inches nominal
 
Related Parts by Category
Related Manufacturers
    
        Certified toAS6081 Methods
    
    
    
    
    
    

    