NSN: 5925-01-260-0462

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • ~1

    data on certain environmental and performanc

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Body Width

    0.719 inches minimum and 0.781 inches maximum

  • Arc Quenching Method

    magnetic blowout

  • Center To Center Distance Between Terminals Parallel To Length

    1.529 inches minimum and 1.591 inches maximum

  • Maximum Continuous Load Current Rating Per Pole

    3.0 amperes dc single location

  • Operating Voltage Type And Rating Per Pole In Volts

    50.0 dc single location

  • Boss Height

    0.099 inches minimum and 0.161 inches maximum

  • Body Style

    single pole type

  • Body Length

    1.969 inches minimum and 2.031 inches maximum

  • Terminal Type And Quantity

    2 tab w/screw

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    1.629 inches minimum and 1.691 inches maximum

  • Case Material

    plastic

  • Specification/Standard Data

    81349-mil-c-55629/7 government specification

  • Trip Release Characteristic

    time delay single location

  • Nominal Thread Size

    0.138 inches

  • Internal Trip Release Configuration

    series trip single location

  • Manual Actuator Type And Quantity

    1 toggle

  • Pole Quantity

    1

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    2000.0 dc single location

  • Circuit Protection Type

    overcurrent single location

  • Thread Quantity Per Inch

    32

  • Mounting Surface To Terminal End Distance

    2.032 inches maximum

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.130 minimum at 200 pct single location and 1.400 maximum at 200 pct single location

  • Actuator Function

    trip-reset

  • Storage Type

    general purpose warehouse

  • Actuator Position Designation

    at pole one

  • Reset Method

    manual

  • Thread Series Designator

    unc

  • Special Handling Feature

    magnetic

  • Trip Release Method

    magnetic single location

  • Fragility Factor

    moderately rugged

  • Test Data Document

    81349-mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...