NSN: 5925-01-375-1254
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
6b multipole-single actuator type
-
Body Length
2.000 inches nominal
-
Case Material
metal
-
Center To Center Distance Between Terminals Parallel To Length
2.323 inches nominal
-
Pole Quantity
2
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Trip Release Method
magnetic all locations
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Ultimate Trip Time Per Pole In Seconds
1.000 minimum all locations and 500.000 maximum
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at pole two
-
Internal Trip Release Configuration
series trip all locations
-
Nominal Thread Size
0.138 inches
-
Trip Release Ambient Temp Rating
-40.0 deg celsius minimum all locations and 85.0 deg celsius maximum
-
Thread Tolerance Class
2b internal
-
Frequency In Hertz
60.0 all locations
-
Test Data Document
81349-mil-c-55629b specification
-
Thread Series Designator
unc
-
Terminal Type And Quantity
4 screw
-
Body Height
2.102 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.530 inches nominal
-
Mounting Facility Type And Quantity
2 threaded hole
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
nontrip free
-
Actuator Function
trip-reset
-
Trip Release Duty Cycle
continuous all locations
-
~1
0.001 minimum at 800 pct and 0.600 maximum at 800 pct and 0.001 minimum at 1000 pct and 0.290 maximum at 1000 pct
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 125 pct all locations and 120.000 maximum at 125 pct and 3.000 minimum at 200 pct and 20.000 maximum at 200 pct and 0.300 minimum at 400 pct and 2.300 maximum at 400 pct and 0.130 minimum at 600 pct and 1.000 maximum at 600 pct and
-
Special Features
no auxiliary contacts
-
Bushing Length
0.625 inches nominal
-
Body Width
1.515 inches nominal
Related Parts by Category
Related Manufacturers


AS6081 Methods