Technical Characteristics
-
Contact Adjustability
deactuation point adjustable and actuation point adjustable
-
Mounting Method
bracket and unthreaded hole
-
Contact Voltage Rating In Volts
115.0 dc at sea level fifth voltage
-
Overall Length
4.875 inches nominal
-
Contact Load Current Rating
3.2 amperes resistive load fourth voltage
-
Contact Voltage Rating In Volts
230.0 ac at sea level second voltage
-
Contact Load Current Rating
4.0 amperes resistive load third voltage
-
Contact Load Current Rating
9.6 amperes resistive load fifth voltage
-
Contact Load Current Rating
8.0 amperes resistive load second voltage
-
Contact Adjustment Type
external deactuation point screw and external actuation point screw
-
Contact Load Current Rating
2.0 amperes resistive load eighth voltage
-
Contact Voltage Rating In Volts
550.0 ac at sea level fourth voltage
-
Nonpile-Up Contact Arrangement
1 two circuit, double break/double make, one position momentary
-
Unthreaded Mounting Hole Diameter
0.281 inches nominal
-
Overall Width
2.625 inches nominal
-
Contact Voltage Rating In Volts
440.0 ac at sea level third voltage
-
Operating Temp Rating
276.0 deg fahrenheit maximum
-
Bulb Length
6.000 inches nominal
-
Contact Adjustment Range
+185.00/+250.00 actuation point degrees fahrenheit and +183.00/+245.00 deactuation point degrees fahrenheit
-
Contact Voltage Rating In Volts
550.0 dc at sea level eighth voltage
-
Capillary Tube Length
128.000 inches nominal
-
Frequency In Hertz
60.0 second voltage
-
Contact Load Current Rating
4.8 amperes resistive load sixth voltage
-
Terminal Type
screw
-
Contact Voltage Rating In Volts
440.0 dc at sea level seventh voltage
-
Contact Load Current Rating
16.0 amperes resistive load first voltage
-
Media For Which Designed
gas or liquid
-
Contact Voltage Rating In Volts
115.0 ac at sea level first voltage
-
Frequency In Hertz
60.0 third voltage
-
Frequency In Hertz
60.0 first voltage
-
Distance Between Mounting Facility Centers
2.406 inches nominal
-
Bulb Diameter
1.125 inches nominal
-
Contact Voltage Rating In Volts
230.0 dc at sea level sixth voltage
-
Features Provided
electrical access port
-
Contact Load Current Rating
2.5 amperes resistive load seventh voltage
-
Contact Action Stimulus
decrease
-
Temp Sensing Element Type
capillary tube
-
Frequency In Hertz
60.0 fourth voltage
-
Mounting Facility Pattern
two position in-line
-
Body Height
2.500 inches nominal