NSN: 5925-01-300-9745

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Trip Release Characteristic

    time delay all locations

  • Center To Center Distance Between Terminals Parallel To Width

    0.625 inches nominal

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Nonturn Device Diameter

    0.140 inches nominal

  • Thread Pitch Diameters

    +0.3503/+0.3537 inches

  • Nominal Thread Size

    0.375 inches

  • Thread Quantity Per Inch

    32

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations and 1000.0 dc all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Trip Release Method

    magnetic all locations

  • Mounting Surface To Terminal End Distance

    1.780 inches maximum

  • Actuator Position Designation

    at pole two

  • Inclosure Protection Type For Which Designed

    hermetically sealed

  • Switch Contact Arrangement

    single pole, double throw

  • Center To Center Distance Between Terminals Parallel To Length

    0.875 inches nominal

  • Nonturn Device Location

    at 3 oclock and at 9 oclock

  • Body Style

    multipole-single actuator type

  • Nonturn Device Radius

    0.625 inches nominal

  • Fragility Factor

    moderately rugged

  • Switch Terminal Type

    tab, solder lug

  • Special Handling Feature

    magnetic

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Reset Method

    manual

  • Mounting Facility Type And Quantity

    1 threaded bushing w/panel seal

  • Storage Type

    general purpose warehouse

  • Switch Location And Position Designation

    internal at pole two

  • Case Material

    metal

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac all locations

  • Manual Actuator Type And Quantity

    1 toggle

  • Body Width

    1.937 inches maximum

  • Main Contact Tripping Mechanism Type

    trip free

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    115.0 all locations

  • Arc Quenching Method

    magnetic blowout

  • Switch Current Rating And Type In Amps

    0.5 ac and 0.5 dc

  • Body Length

    1.562 inches maximum

  • Frequency In Hertz

    400.0 all locations

  • Thread Series Designator

    unef

  • Switch Voltage Rating And Type In Volts

    120.0 ac and 50.0 dc

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Terminal Type And Quantity

    6 tab w/screw

  • Unpackaged Unit Weight

    5.400 ounces

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.150 minimum at 200 pct all locations and 0.600 maximum at 200 pct all locations

  • Bushing Length

    0.380 inches maximum

  • Nonturn Device Length

    0.130 inches nominal

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.